The practical answer: assess a high-speed connection using its negotiated FEC mode, link state and supported counters over a known observation interval. Corrected errors do not automatically mean that an application received damaged data; a zero in one field does not prove the whole network is healthy. Interpret results using documentation for the exact adapter, switch and firmware, and preserve the evidence before making changes.

Forward error correction is a physical-layer mechanism, not a substitute for checking RDMA, queues or application behaviour. This guide covers evidence collection for the physical link. It sets no universal error threshold and does not recommend changing modes or clearing counters on a production fabric without coordination.

The speed in an adapter name describes capabilities of a particular implementation. A working link also depends on both ports, transceivers or direct-attach cable, protocol mode, settings and supported software versions. An incompatible component can result in a lower negotiated rate, instability or no link. A matching external connector name is not a sufficient compatibility check.

Start with a connection record: source and destination ports, function, expected rate, protocol, cable type, length and optics part numbers. Record the adapter and switch models, firmware and driver versions, and timestamps. Establish which fields are available in the installed tools. Compare values from different devices only after checking that their units and definitions match.

NVIDIA Firmware Tools documentation describes mlxlink, including --show_counters for physical counters and BER information. The exact options and fields must be checked against the installed release and supported device. A documentation link does not imply that every command or counter is available on every adapter.

Corrected and uncorrected observations

In broad terms, FEC adds redundancy that can help the receiver correct certain transmission errors. Diagnostic fields may distinguish observed or corrected errors from events that could not be corrected. Names, units, observation windows and counter behaviour depend on the implementation.

A corrected event does not necessarily mean that an application received corrupted data. A sustained change in a relevant counter can still justify checking the link and its trend against vendor guidance. Conversely, no change in that counter does not exclude problems elsewhere in the network or above the physical layer. Do not apply the same threshold to unrelated devices or firmware without confirmation.

Separate a cumulative counter from an event rate and from an estimated bit error rate. If the documentation does not define a field, do not call it lost packets or failed requests. Establish whether a field applies to one lane, the whole port or another grouping; matching labels in different tools do not guarantee matching scope. Decision-making needs observations from both ends, change history and a physical-port mapping.

What to preserve in a baseline

Item Why it belongs in the record
Ports and protocol Connect the observation to the physical route
Negotiated rate and FEC mode Confirm the intended configuration is active
Model, firmware and driver Identify available fields and comparison limits
Optics, cable, length and breakout Check physical compatibility
Counter snapshots and timestamps Calculate a change over a known interval
Workload type and intensity Compare equivalent operating conditions
Link events and restarts Explain whether counters may have reset

Exclude secrets, management addresses and other data unnecessary to the recipient. Store raw diagnostic output according to the organisation's access and sharing process.

Worked counter example

Suppose a supported cumulative counter reads 1,000 at the beginning and 1,180 after 30 minutes. If the device and counter did not reset, the change is 1,180 − 1,000 = 180 events over 30 minutes, or an average of 6 per minute. This illustrates arithmetic; it is not a recommended 800G limit.

An average can hide a short burst. Capture a sequence of samples and link-state events when appropriate. If a restart, reset or rollover occurred, simple subtraction may be invalid. If the documented metric is already a rate or BER, do not treat it as a cumulative event count without checking the definition.

Compare multiple equal-duration intervals at idle and under an agreed workload. Differences between connections may indicate where further checking is useful, but do not automatically identify the cause. The manufacturer's documentation and support process determine how to assess the observation.

Compare both ends under a known load

Check the negotiated rate and FEC mode on the adapter and the switch. Capture link state, errors and changes over corresponding intervals, and mark fields that cannot be read on a given device. When vendors use different names, determine whether the fields represent the same event before comparing them. A cumulative counter at one endpoint and BER at the other cannot simply be added.

Run approved traffic checks in an isolated environment or a coordinated maintenance window. For AI infrastructure, validate the link and the target application's communication separately: a stable physical connection does not guarantee correct RDMA configuration or balanced traffic across all paths. Record message sizes, stream count, duration and targets so another engineer can repeat the observation.

Inspect optics, connectors and routes using the facility's and manufacturer's procedures. Do not replace components or change FEC mode on a live connection without approval; it can interrupt traffic. Clearing counters before saving the readings removes useful evidence.

Handing the evidence to the next shift

Record the original counter readings as well as their difference, with a timestamp and time zone for each observation. Identify the device, local port, peer port and link state. Note firmware updates, cable changes and restarts during the interval: a counter may have restarted. Do not compare fields merely because their names contain “error.” Include the workload description and the relevant device documentation in the escalation package, removing sensitive details according to your organisation's process.

Escalation package

Provide the supplier with device part numbers, connection diagram, compatible software versions, time series and workload description. State whether symptoms were observed at both ends, whether the port mode changed and whether either device restarted. Apply any threshold only to the device and release for which the manufacturer documents it.

Do not declare a particular module defective until the diagnosis follows the supplier's procedure. A useful result is a reproducible evidence set, agreed criteria and a safe next step.